A plain-English guide to DSEAR zones, ATEX and UKEX marking, gas groups and T classes, and why a sealed IP65 keyboard is not the same as one certified for a hazardous area.
iKey intrinsically safe keyboards for hazardous areas

Every so often an enquiry comes in that starts with "we need a rugged keyboard for the plant" and, a couple of emails later, it turns out the keyboard is going into an area where there could be flammable gas or combustible dust in the air. That changes the conversation completely. At that point toughness and sealing are not the main question. The main question is whether the keyboard could ignite the atmosphere around it.

Hazardous area equipment is a specialist subject, and it is easy to get lost in the codes and acronyms. This guide covers the basics in plain English, explains what the markings mean, and is honest about what we do and do not have on the site.

One thing first: this is a starting point, not a substitute for your site's hazardous area classification or your safety engineer. If you are not sure which zone you are working in, that needs settling before anyone chooses a keyboard.

Why ordinary keyboards are a problem in explosive atmospheres

Any electrical device can, in the wrong conditions, create a spark or a hot surface. The HSE puts it simply: using electricity can generate hot surfaces or sparks which can ignite an explosive atmosphere. It gives examples such as paint spray booths, the area near fuel tanks and sumps.

A keyboard is a low-power device, but it still has a circuit board, a cable and a connection to a computer that is usually not low power at all. In a hazardous area, the HSE's guidance is that equipment must be specially designed and constructed so that the risk of ignition is eliminated or reduced.

The UK rules in brief: DSEAR, zones and markings

In the UK, the Dangerous Substances and Explosive Atmospheres Regulations (DSEAR) require employers to assess the risk and classify areas where explosive atmospheres may occur. Those areas are divided into zones. The HSE's guidance on hazardous area classification defines them like this:

  • Zone 0: an explosive gas atmosphere is present continuously or for long periods
  • Zone 1: an explosive gas atmosphere is likely to occur in normal operation
  • Zone 2: an explosive gas atmosphere is not likely to occur in normal operation, and if it does, only for a short time
  • Zones 20, 21 and 22 are the equivalents for combustible dust clouds

Each zone calls for a minimum equipment category. Zone 0 needs Category 1 equipment, Zone 1 needs Category 2 and Zone 2 needs Category 3. The Fire Industry Association's guide to equipment for explosive atmospheres sets out the same mapping for dust, so Zone 20 needs Category 1D, Zone 21 needs 2D and Zone 22 needs 3D.

On marking, the HSE says equipment placed on the market in Great Britain must be UKCA or CE marked, supplied with a Declaration of Conformity and have instructions in English, and that most new equipment sold in the UK for these areas must have an ATEX certificate. Recently installed equipment should also carry the Ex mark. You will often hear the UK version of the scheme called UKEX.

Gas groups and temperature classes

Two more parts of the marking matter when you are matching equipment to a site.

Gas groups

Gases are grouped by how easily they ignite. According to the FIA guide:

  • IIA covers gases such as propane, methane, ethanol and acetone
  • IIB covers gases such as ethylene and hydrogen sulphide
  • IIC covers the easiest to ignite, such as hydrogen and acetylene

As the FIA guide puts it, group C requires the highest degree of protection and group A the lowest, so check the group on the equipment matches or exceeds the gas on your site. Dusts have their own groups (IIIA for combustible fibres, IIIB for non-conductive dusts and IIIC for conductive dusts).

Temperature classes

The T rating tells you the maximum surface temperature the equipment can reach. The HSE lists six classes, from T1 at 450°C down to T6 at 85°C. The equipment's T class has to be below the ignition temperature of whatever substance is present on your site.

Where IECEx fits in

You will also see IECEx on data sheets. It is an international certification scheme, described by the IEC as an international certification initiative that ensures the safety and compliance of electrical and mechanical equipment. An IECEx certificate makes it much easier to get products approved in different countries, but it is not the same thing as the legal UK or EU marking. For a UK site, the thing to look for is still the UKCA or CE marking with the Ex mark.

IP65 does not mean safe for a hazardous area

This is the misunderstanding we come across most. A keyboard that is sealed to IP65 or IP68, or rated NEMA 4X, is protected against dust and water getting in. That is an ingress protection rating. It says nothing about whether the keyboard could ignite a flammable atmosphere.

Plenty of excellent industrial keyboards, including many on this site, are completely sealed and almost indestructible, and they are still not suitable for Zone 1 or Zone 2. The keyboard has to carry its own hazardous area certification for the zone, gas or dust group and temperature class it will be used in. If it does not say so on the label and the certificate, assume it is not.

The intrinsically safe keyboards on our site

Intrinsically safe (IS) equipment works by limiting the electrical and thermal energy in the circuit so that it cannot ignite the atmosphere, even if something goes wrong. iKey makes a range of stainless steel IS keyboards that we list on the site:

  • The iKey DT-1000-IS is a full-size stainless steel desktop keyboard with a sealed silicone keypad, 24 function keys and a numeric pad.
  • The iKey DT-5K-IS is a more compact stainless steel keyboard with an integrated HulaPoint pointing device.
  • The iKey DT-5K-FSR-IS is the same idea with a force sensing resistor pointer.
  • For consoles and enclosures there are panel mount versions, including the PM-1000-IS and the PM-2000-IS.

These units come with optical isolated barriers and bulkhead cables. Here is the important bit, though. iKey's intrinsically safe range carries Factory Mutual (FM) approval for Class I, II and III, Division 1, Groups C, D, E, F and G. That is the North American Class and Division system, not ATEX or UKEX. iKey's product information does not list ATEX or IECEx certification for these models.

So if your site is in North America, or your project specifies FM approval, they may be exactly what you need. If your site is in the UK or EU and classified under DSEAR or ATEX zones, do not assume an FM approval covers you. Talk to your safety engineer, and talk to us, before ordering.

Practical tips before you buy

  • Get the zone in writing. Ask for the zone, the gas or dust group and the temperature class from your hazardous area classification drawing. Without those three, nobody can recommend equipment responsibly.
  • Think about the whole system. A certified keyboard is only part of it. The barrier, the cable route and the computer it connects to all need to be considered, often with the PC sitting outside the hazardous area.
  • Ask for the certificate, not just the data sheet. The certificate shows exactly what the product is approved for.
  • Consider moving the keyboard out of the zone. Sometimes the simplest answer is to put the operator station just outside the classified area and use a standard rugged keyboard there.
  • Plan for inspection. The HSE expects equipment in these areas to be inspected and maintained by competent people, so factor that into the installation.

Talk to us about your hazardous area project

Hazardous area keyboards are not something to guess at. If you send us the zone, the gas or dust group and the temperature class, we will tell you honestly what we can supply and whether it fits. Send us your requirements and we usually reply within 24 hours.

If your keyboard will sit outside the classified area, have a look at our industrial and manufacturing keyboards and our stainless steel keyboards.

Thank you

Thank you for taking the time to read our post about Keyboards for Hazardous Areas: ATEX and Intrinsically Safe Explained. We truly appreciate your interest in our content! bestkeyboards.co.uk strives to be the ultimate destination for anyone seeking comprehensive information on computer keyboards. If you found this blog post, Keyboards for Hazardous Areas: ATEX and Intrinsically Safe Explained enjoyable and informative, we would be grateful if you could leave a comment below and share it with your friends and colleagues. Your feedback and support mean a great deal to us and are what drive us to continue producing high-quality content for you. Please don't hesitate to reach out to us with any questions, comments, or suggestions for future blog topics. We truly value your input and love hearing from our readers.